Fire safety guidance on artificial foliage in commercial premises

Section

Fire performance standards and test methods

There is currently no specific British Standard, European standard or recognised test method for assessing the fire performance of artificial foliage. In the absence of a dedicated standard or test method, this guidance considers existing standards and guidance that may provide useful reference points when assessing the fire performance of artificial foliage.  The relevance and limitations of some of these standards and guidance to artificial foliage are considered below.

Approved Document B

For buildings under construction and existing buildings undergoing work subject to the Building Regulations, there is a requirement (B2) for the linings of walls and ceilings to adequately resist the spread of flame over their surfaces. To assist designers in complying with this requirement, Table 6.1 of Approved Document B Volume 2 provides guidance on the fire performance of materials used to line surfaces based on classification under BS EN 13501-1. The expected minimum fire performance varies depending on the size and use of the space within the building.

Approved Document B (fire safety) Volume 2: Buildings other than dwellings

Table 6.1 Classification of linings

Location Classification
Small rooms of maximum internal floor area:

a)      4m2 in residential accommodation

b)     30m2 in non-residential accommodation

D-s3,d2
Other rooms (including garages) C-s3, d2
Other circulation spaces B-s3, d2(1)
Note:

Wallcoverings which conform to BS EN 15102, achieving at least class C-s3,d2 and bonded to a class A2,s3, d2 substrate, will also be acceptable

 

 

Although the Building Regulations and Approved Document B do not generally address decorative items such as artificial foliage, the principles relating to the reaction-to-fire performance of surface linings provide a useful reference point. This approach is also reflected in Fire safety risk assessment: small and medium places of assembly, which identifies the potential for materials used to line walls and ceilings to contribute significantly to the spread of flame and refers to Approved Document B and BS EN 13501-1 for further information on internal linings and fire classifications.

The use of Approved Document B as a reference point should not, however, be taken to mean that artificial foliage is a building lining or that the classifications in Table 6.1 can be directly applied to it. Artificial foliage can be very different from conventional surface linings in terms of construction, how it is arranged and fixed and how it may be exposed to fire.

BS 9999

BS 9999 provides guidance on decorative features that explicitly includes artificial foliage. It states that materials should not present an unacceptable increase in combustible materials within a building or cause rapid fire spread or smoke generation if involved in a fire. BS 9999 recommends that decorative features should either be non-combustible or conform to the requirements for Type B classification in accordance with BS 5867-2:2008, following the appropriate wetting or cleansing procedure described in BS 5651.

BS 5867-2 covers the flammability performance of fabrics used for curtains, drapes and window blinds. Although it was not developed specifically for artificial foliage, there may be similarities in some applications and may therefore provide a useful reference point.  The wetting or cleansing procedure in BS 5651 is intended to establish whether the required fire performance of fabrics, including the effectiveness of any flame-retardant treatment, is maintained following cleaning or other conditioning. The applicability of this procedure to artificial foliage may therefore be limited, particularly for products manufactured from non-absorbent plastics.

Other test standards

In developing this guidance, NFCC has identified other standards being referenced in support of claims regarding the fire performance of artificial foliage. These standards were developed for other products or applications and are not specific to artificial foliage. However, as they may be encountered when considering the fire performance of artificial foliage, some background on their purpose and limitations is provided below.

  • BS EN 15102 covers decorative wallcoverings and provides a means of classifying fire performance without fire testing, subject to certain criteria. The scope of this standard is limited to coverings supplied in roll form and are hung to walls or ceilings using an adhesive.  The classification also applies only to wallcoverings with a limited weight and a thickness of less than 2 mm. These would not generally be representative of artificial foliage.
  • BS 5852 provides a method of testing the ignitability of upholstered seating. In many cases, references to BS 5852 are made in support of the fire-retardant treatments which may be applied to artificial foliage to improve fire performance.  It should not be assumed that the same level of performance will be achieved when the treatment is applied to artificial foliage, which will likely comprise different materials in a different arrangement.

Inherently flame-retardant materials and flame-retardant treatments

Artificial foliage may be manufactured using materials or additives intended to provide flame-retardant properties as part of the manufacturing process. Such products are sometimes described as “inherently flame-retardant” (IFR). However, IFR is not itself a defined fire performance classification or test standard, and the term should not be taken as evidence of a particular level of fire performance.

Where artificial foliage has not been manufactured to achieve a defined level of reaction-to-fire performance, an alternative approach to reduce the risk of ignition and fire spread may be to apply a flame-retardant treatment. Such treatments can take the form of a spray or dip and may be applied after manufacture or installation. Flame-retardant treatments do not all work in the same way. Depending on the product, the treatment may be intended to penetrate or be absorbed into the material or form a protective layer on its surface. The effectiveness and durability of the treatment may therefore depend on the material to which it is applied. This is particularly relevant to artificial foliage, which is commonly manufactured from plastics and other non-absorbent materials. Where a treatment is applied to such materials, it should not be assumed that one developed for an absorbent material will provide equivalent performance.

Assessing fire performance claims

Claims that an artificial foliage product or flame-retardant treatment complies with a recognised fire performance standard should be supported by appropriate test evidence or certification. For example, there are companies marketing artificial foliage as “Class B” or “fire-rated”. Generic marketing statements or declarations of compliance, without supporting documentation, should not be relied upon.

Given the limitations associated with the standards and test methods described above, evidence of compliance should be considered carefully to establish whether it provides meaningful information about the fire performance of the installed product.

Enforcing authorities should seek evidence that establishes:

  • the product, material or treatment tested
  • the standard and test conditions applied
  • the results achieved
  • whether the tested specimen is representative of the materials, construction and treatment of the installed product.

Consideration should also be given to whether the evidence relates to how the product will be used and installed, including how it is mounted, its orientation and the substrate it is fixed to.